- 33
- MESSAGE
UPS LDEV ! reports loss of AC input power. (UPSERR 0033)
- CAUSE
The specified UPS device reported that it detected an input power failure. There has been an AC power failure somewhere in the power path leading into the UPS. The UPS has switched to its internal battery pack to supply reserve power. - ACTION
If the power failure is brief, not long enough to exhaust the UPS battery, no action is needed. Otherwise, determine what is causing the power loss and take action to restore the power before the UPS battery becomes exhausted.
- 35
- MESSAGE
UPS LDEV ! reports AC input power "Bypass Mode". (UPSWRN 0035)
- CAUSE
The specified UPS device has been placed into its "AC Power Bypass Mode" of operation. This should only occur when an HP Customer Engineer is servicing the UPS and intends to put the UPS into "Bypass Mode".
- ACTION
No action is needed if this message occurs during Customer Engineer servicing of the UPS.If this message occurs during normal system operation, there is probably a hardware problem in the UPS. Call your HP service representative.
- 36
- MESSAGE
UPS LDEV ! reports AC input power restored. (UPSWRN 0036) - CAUSE
The specified UPS device had lost its AC input power in the past, and
now the AC input power has been restored. If the UPS is operating correctly, it will now switch from battery operation back to normal AC power operation.
- ACTION
No action is needed. The system automatically returns to normal operation when all UPS devices (there may be one or several UPS devices on a system) detect that normal AC input power is present following a power loss at any UPS.
- 37
- MESSAGE
UPS LDEV ! reports "Low Battery Charge" condition. (UPSWRN 0037)
- CAUSE
The specified UPS had lost its AC input power some time ago and has been supplying reserve power from its battery. AC input power has not been restored yet, causing the battery to be drained down to a "low charge" power level. - ACTION
Locate and correct the cause of the AC power failure. If AC power is not restored within the next two minutes, the UPS battery will be exhausted and the UPS output AC power will fail, causing power loss to the computer equipment.
- 41
- MESSAGE
UPS LDEV ! reports AC output power turned off. (UPSERR 0041)
- CAUSE
The specified UPS device has turned off its AC output power. Someone may have mistakenly turned off the UPS' power switch, or the UPS may have malfunctioned. Whatever equipment was receiving power from the UPS has now lost power. - ACTION
Investigate and correct the problem at the UPS. Turn on all power control switches on the UPS. If the computer (CPU) lost power, you will have to re-boot the system after restoring the UPS power.
- 128
- MESSAGE
UPS LDEV ! reports UPS "System Fail" condition cleared. (UPSWRN 0128)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "System Failure" condition. Now, the "System Failure" condition within the UPS device has been corrected and the UPS is reporting that it has returned to normal operation. - ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 129
- MESSAGE
UPS LDEV ! reports UPS "Inverter Fail" condition cleared. (UPSWRN 0129)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Inverter Failure" condition. Now, the "Inverter Failure" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation. - ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 130
- MESSAGE
UPS LDEV ! reports UPS "Battery Not Present" condition cleared. (UPSWRN 0130)
- CAUSE
Some time ago, the specified UPS device had reported a "Battery Not Present" condition. Now, the "Battery Not Present" condition within the UPS has been corrected and the UPS is reporting that it has returned to normal operation. - ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 131
- MESSAGE
UPS LDEV ! reports UPS "Charger Fault" condition cleared.
(UPSWRN 0131)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Charger Fault" condition. Now, the "Charger Fault" condition within the UPS device has been corrected and the UPS is reporting that it has returned to normal operation. - ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 132
- MESSAGE
UPS LDEV ! reports UPS "Overload Shutdown" condition cleared. (UPSWRN 0132)
- CAUSE
Some time ago, the specified UPS device had reported an "Overload Shutdown" condition. Now, the "Overload Shutdown" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 133
- MESSAGE
UPS LDEV ! reports UPS "High Ambient Temperature Shutdown"
condition cleared. (UPSWRN 0133)
- CAUSE
Some time ago, the specified UPS device had reported a "UPS High Ambient Temp- erature Shutdown" condition. Now, the "High-Ambient Temperature Shutdown" con- dition has been corrected. The UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 134
- MESSAGE
UPS LDEV ! reports UPS "Overload" condition cleared. (UPSWRN 134)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Overload"
condition. Now, the UPS "Overload" condition has been corrected and the UPS
is reporting that it has returned to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported
problem has been corrected.
- 135
- MESSAGE
UPS LDEV ! reports UPS "High Ambient Temperature" condition
cleared. (UPSWRN 0135)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "High Ambient Temp- erature" condition. Now, the "High Ambient Temperature" condition has been corrected and the UPS is reporting that it has returned to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 136
- MESSAGE
UPS LDEV ! reports UPS "Battery Test Fail" condition cleared. (UPSWRN 0136)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Battery Test Fail" condition. Now, the "Battery Test Fail" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 137
- MESSAGE
UPS LDEV ! reports UPS "High Battery Voltage" condition cleared.
(UPSWRN 0137)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "High Battery Volt- age" condition. Now, the "High Battery Voltage" condition in the UPS device has been corrected and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 138
- MESSAGE
UPS LDEV ! reports UPS "Low Battery Voltage" condition cleared.
(UPSWRN 0138)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Low Battery Volt- age" condition. Now, the "Low Battery Voltage" condition in the UPS device has been corrected and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 139
- MESSAGE
UPS LDEV ! reports UPS "High Output Voltage Shutdown" condition cleared. (UPSWRN 0139)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "High Output Volt- age Shutdown" condition. Now, the "High Output Voltage Shutdown" condition has been cleared and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 140
- MESSAGE
UPS LDEV ! reports UPS "Low Output Voltage Shutdown" condition cleared. (UPSWRN 0140)
- CAUSE
Some time ago, the specified UPS device had reported a UPS "Low Output Voltage Shutdown" condition. Now, the "Low Output Voltage Shutdown" condition has been corrected and the UPS is reporting a return to normal operation.
- ACTION
No action is needed. This message merely confirms that a previously reported problem has been corrected.
- 192
- MESSAGE
UPS LDEV ! reports UPS "System Fail" condition. (UPSERR 0192)
- CAUSE
The specified UPS device reported a UPS "System Failure" condition.
This is a hardware malfunction condition within the UPS.
- ACTION
Call your Hewlett-Packard service representative.
- 193
- MESSAGE
UPS LDEV ! reports UPS "Inverter Fail" condition. (UPSERR 0193)
- CAUSE
The specified UPS device reported a "UPS Inverter Fail" condition.
This is a hardware malfunction condition within the UPS. The DC-to-AC power inverter within the UPS has malfunctioned.
- ACTION
Call your Hewlett-Packard service representative.
- 194
- MESSAGE
UPS LDEV ! reports UPS "Battery Not Present" condition. (UPSERR 0194)
- CAUSE
The specified UPS device reported a "Battery Not Present" condition.
This is a hardware malfunction condition within the UPS. The UPS hardware logic perceives that the UPS battery pack is not connected. - ACTION
Call your Hewlett-Packard service representative.
- 195
- MESSAGE
UPS LDEV ! reports UPS "Charger Fault" condition. (UPSERR 0195)
- CAUSE
The specified UPS device reported a UPS "Charger Fault" condition.
This is a hardware malfunction condition within the UPS. The UPS' internal battery charger circuitry has malfunctioned.
- ACTION
Call your Hewlett-Packard service representative.
- 196
- MESSAGE
UPS LDEV ! reports UPS "Overload Shutdown" condition. (UPSERR 0196) \CAUSE\ The specified UPS device reported a UPS "Overload Shutdown" condition. Too much power was being drawn from the UPS AC output by the computer equipment being powered from this UPS. That equipment may be malfunctioning. - ACTION
Call your Hewlett-Packard service representative.
- 197
- MESSAGE
UPS LDEV ! reports UPS "High Ambient Temperature Shutdown"
condition. (UPSERR 0197) - CAUSE
The specified UPS device reported a UPS "High Ambient Temperature Shutdown" condition. The temperature of the UPS hardware became too high to permit safe operation, and the UPS turned itself off to prevent equipment damage. - ACTION
If the computer room has become too warm, take steps to cool the room. If room temperature is not the problem, there has probably been a hardware malfunction. Call your Hewlett-Packard service representative.
- 198
- MESSAGE
UPS LDEV ! reports UPS "Overload" condition. (UPSERR 0198)
- CAUSE
The specified UPS device reported a UPS "Overload" condition. The equipment being powered by the UPS is drawing too much power from the UPS AC output. If the excessive power draw continues, the UPS may reach an "Overload Shutdown". - ACTION
Call your Hewlett-Packard service representative.
- 199
- MESSAGE
UPS LDEV ! reports UPS "High Ambient Temperature" condition. (UPSERR 0199)
- CAUSE
The specified UPS device reported a UPS "High Ambient Temperature" condition. The UPS has detected an abnormally high temperature in the UPS hardware. If the temperature rises further, the UPS may reach "High Temperature Shutdown". - ACTION
If the computer room has become too warm, take steps to cool the room. If room temperature is not the problem, there has probably been a hardware malfunction. Call your Hewlett-Packard service representative.
- 200
- MESSAGE
UPS LDEV ! reports UPS "Battery Test Fail" condition. (UPSERR 0200)
- CAUSE
The specified UPS device reported a UPS "Battery Test Fail" condition.
This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly. - ACTION
Call your Hewlett-Packard service representative.
- 201
- MESSAGE
UPS LDEV ! reports UPS "High Battery Voltage" condition. (UPSERR 0201)
- CAUSE
The specified UPS device reported a UPS "High Battery Voltage" condition. This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly. - ACTION
Call your Hewlett-Packard service representative.
- 202
- MESSAGE
UPS LDEV ! reports UPS "Low Battery Voltage" condition. (UPSERR 0202)
- CAUSE
The specified UPS device reported a UPS "Low Battery Voltage" condition. This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly. - ACTION
Call your Hewlett-Packard service representative.
- 203
- MESSAGE
UPS LDEV ! reports UPS "High Output Voltage Shutdown" condition. (UPSERR 0203)
- CAUSE
The specified UPS device reported a UPS "High Output Voltage Shutdown" condi-tion. This is a hardware malfunction within the UPS hardware or possibly in the equipment being powered from the UPS. The UPS has shut itself off.
- ACTION
Call your Hewlett-Packard service representative.
- 204
- MESSAGE
UPS LDEV ! reports UPS "Low Output Voltage Shutdown" condition. (UPSERR 0204)
- CAUSE
The specified UPS device reported a UPS "Low Output Voltage Shutdown"
condition. This is a hardware malfunction within the UPS hardware or possibly
in the equipment being powered from the UPS. The UPS has shut itself off.
- ACTION
Call your Hewlett-Packard service representative.
- 512
- MESSAGE
UPS Monitor UPS error: Lost communications with UPS LDEV !.
That UPS is no longer being monitored. (UPSERR 0512)
- CAUSE
The UPS Monitor had been monitoring the specified UPS LDEV successfully, then
for some reason lost I/O communications with that UPS. The I/O interface cable
or I/O interface hardware may have failed, or the UPS itself may have failed.
- ACTION
Check the specified UPS's I/O interface cable and I/O interface connection at
the computer. Check the UPS hardware for power connections and front panel
indicators. If the cause is not found, call your HP service representative.
- 513
- MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS
power status condition. (UPSERR 0513)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 514
- MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS alarm
status condition. (UPSERR 0514)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 515
- MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS status
kind. (UPSERR 0515)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 516
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Receive_Msg. (UPSERR 0516)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 517
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Sendio. (UPSERR 0517)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 518
- MESSAGE
UPS Monitor logic error: Invalid UID in UPS Table Entry when
starting next UPS I/O request. (UPSERR 0518)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 519
- MESSAGE
UPS Monitor logic error: Invalid UPS Number in UPS Table Entry
when starting next UPS I/O request. (UPSERR 0519)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 520
- MESSAGE
UPS Monitor logic error: Attempt to specify "no I/O request" when
starting next UPS I/O request. (UPSERR 0520)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 521
- MESSAGE
UPS Monitor logic error: Invalid Read request count when
starting next UPS I/O request. (UPSERR 0521)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative
- 522
- MESSAGE
UPS Monitor logic error: Invalid I/O function specified
when starting next UPS I/O request. (UPSERR 0522)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 523
- MESSAGE
UPS Monitor logic error: Attempt to start next UPS I/O
request when previous UPS I/O request still running. (UPSERR 0523)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 524
- MESSAGE
UPS Monitor logic error: Attempt to start more UPS I/O requests
than there are UPS devices being monitored. (UPSERR 0524)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 525
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Rel_IO_Resources. (UPSERR 0525)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 526
- MESSAGE
UPS Monitor logic error: I/O reply message received, not
expected in present UPS operating state. (UPSERR 0526)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 527
- MESSAGE
UPS Monitor logic error: I/O reply message received, but
UPS operating state is undefined/unknown. (UPSERR 0527)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 528
- MESSAGE
UPS Monitor logic error: UPS operating substate invalid
while processing a "Go Online" I/O completion. (UPSERR 0528)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 529
- MESSAGE
UPS Monitor logic error: UPS operating substate invalid
while processing a "Set Terminal Controls" I/O completion. (UPSERR 0529)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 530
- MESSAGE
UPS Monitor logic error: UPS number invalid in UID of I/O
Reply message. (UPSERR 0530)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 531
- MESSAGE
UPS Monitor logic error: Underflow of a UPS's number of I/O
requests outstanding when processing a UPS I/O completion. (UPSERR 0531)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 532
- MESSAGE
UPS Monitor logic error: Underflow of global number of UPS
I/O requests outstanding when processing a UPS I/O completion. (UPSERR 0532)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 533
- MESSAGE
UPS LDEV ! I/O Operation warning: Warning status returned by
I/O system at completion of a UPS I/O request. (UPSWRN 0533)
- CAUSE
This is a software-detected warning condition that indicates something unusual
occurred in an I/O request made to a UPS by the UPS Monitor.
- ACTION
If this warning appears only rarely, then no action is needed. If it appears
frequently, then call your Hewlett-Packard service representative.
- 534
- MESSAGE
UPS LDEV ! I/O Operation error: Error status returned by
I/O system at completion of a UPS I/O request. (UPSERR 0534)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
- ACTION
If this error appears only rarely, then no action is needed. If it appears
frequently, then call your Hewlett-Packard service representative.
- 535
- MESSAGE
UPS LDEV ! I/O Operation error: A status of "aborted" was
returned by I/O system as completion status of a UPS I/O request. (UPSERR
0535)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
- ACTION
If this error appears only rarely, then no action is needed. If it appears
frequently, then call your Hewlett-Packard service representative.
- 536
- MESSAGE
UPS LDEV ! I/O Operation error: UPS device failed to complete a
Read I/O request in allotted time. The Read request timed out. (UPSERR 0536)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
It could indicate a disconnected I/O cable or a UPS hardware malfunction.
- ACTION
Check for proper connection of the UPS I/O interface cable at both ends. See
if the UPS is powered-on. If those checks do not reveal the source of the
problem, then call your Hewlett-Packard service representative.
- 538
- MESSAGE
UPS Monitor logic error: UPS operating substate invalid
while processing a "Monitoring" I/O completion. (UPSERR 0538)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 539
- MESSAGE
UPS Monitor logic error: A UPS I/O completion reply message
was received when none was expected, or the message received was not the one
that was expected. (UPSERR 0539)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 540
- MESSAGE
UPS Monitor UPS initialization: UPS LDEV ! was initialized
successfully and is now being monitored. (UPSWRN 0540)
- CAUSE
During system startup, the specified UPS device was successfully initialized
by the UPS Monitor.
- ACTION
No action is needed. This is merely an expected confirmation that the UPS and
UPS Monitor software are operating correctly.
- 541
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Send_Msg. (UPSERR 0541)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 542
- MESSAGE
UPS Monitor logic error: A UPS I/O reply message was received
unexpectedly. The operating state of the UPS Monitor is inappropriate for
receiving an I/O completion reply message. (UPSERR 0542)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 543
- MESSAGE
UPS Monitor logic error: Processing of a UPS I/O completion
message resulted in an unknown/undefined "io_result" variable. (UPSERR 0543)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 544
- MESSAGE
UPS Monitor logic error: An invalid message was received by
the UPS Monitor at its message port. The message is not recognized as any of
the UPS Monitor's message types. (UPSERR 0544)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 545
- MESSAGE
UPS Monitor logic error: An event message of invalid type
was received by the UPS Monitor. The message is recognized as an event
message, but the kind of event is unknown. (UPSERR 0545)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 546
- MESSAGE
:
UPS Monitor logic error: A timer message of invalid type
was received by the UPS Monitor. The message is recognized as a timer
message, but the kind of timer is unknown. (UPSERR 0546)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 547
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Timer. (UPSERR 0547)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 548
- MESSAGE
UPS Monitor logic error: UPS Monitor attempted to process a
timer event message of an invalid type. (UPSERR 0548)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 549
- MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an "invalid number of
UPS's configured" condition in its global table. (UPSERR 0549)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 550
- MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an "invalid number of
UPS's monitored" condition in its global table. (UPSERR 0550)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 551
- MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected a Nil UPS Table Pointer
condition in its global table. (UPSERR 0551)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 552
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Abortio_Request. (UPSERR 0552)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 553
- MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an invalid UPS Table
Entry. (UPSERR 0553)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 554
- MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an invalid count of UPS
I/O requests outstanding. (UPSERR 0554)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 555
- MESSAGE
UPS Monitor logic error: During shutdown processing, the
UPS Monitor found that the UPS Monitor operating state was invalid when the
shutdown event message was received. (UPSERR 0555)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 556
- MESSAGE
UPS Monitor logic error: During shutdown processing, the
UPS Monitor found that a shutdown operation was already in progress. (UPSERR
0556)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 557
- MESSAGE
UPS Monitor logic error: During shutdown processing, when
attempting to start the shutdown limit timer, the UPS Monitor found that a
shutdown limit timer was already running. (UPSERR 0557)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 558
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Release_Timer. (UPSERR 0558)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 559
- MESSAGE
UPS Monitor logic error: During UPS I/O completion processing in
the "Set Terminal Controls" sequence, an I/O reply message was received that
was not of the expected (Terminal Control) type. (UPSERR 0559)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 560
- MESSAGE
UPS Monitor logic error: While processing an I/O Write
completion, an I/O reply message was received that was not of the expected
(Write) type. (UPSERR 0560)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 561
- MESSAGE
UPS Monitor logic error: While processing an I/O Read
completion, an I/O reply message was received that was not of the expected
(Read) type. (UPSERR 0561)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 562
- MESSAGE
UPS LDEV ! I/O Operation error: The actual Write data
transfer length in a UPS Write I/O operation was not the expected (requested)
transfer length. (UPSERR 0562)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
- ACTION
Call your Hewlett-Packard service representative.
- 563
- MESSAGE
UPS LDEV ! I/O Operation error: The actual Read data
transfer length in a UPS Read I/O operation was too short, less than the
minimum required Read transfer length. (UPSERR 0563)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
It could also indicate an I/O interface hardware error, or a UPS hardware error
- ACTION
Call your Hewlett-Packard service representative.
- 564
- MESSAGE
UPS LDEV ! I/O Operation error: The actual Read data
transfer length in a UPS Read I/O operation was too long, greater than the
maxmimum requested Read transfer length. (UPSERR 0564)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
It could also indicate an I/O interface error or a UPS hardware error.
- ACTION
Call your Hewlett-Packard service representative.
- 565
- MESSAGE
UPS Monitor logic error: UPS Monitor found global timer_id
of zero, which is invalid, when it attempted to release the shutdown limit
timer. (UPSERR 0565)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 566
- MESSAGE
UPS Monitor logic error: UPS Monitor detected invalid
parameters in a call to one of its procedures that inspects UPS Read data for
matching to expected UPS input data patterns. (UPSERR 0566)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 567
- MESSAGE
UPS LDEV ! I/O operation error: Data supplied by the UPS
device in response to a Read I/O request did not match any of the allowable
data patterns for that request. The Read will be re-done. (UPSERR 0567)
- CAUSE
Possibly a poor I/O interface cable connection between the system and the UPS.
Possibly electrical noise interference induced in the I/O interface cable or
hardware. It could also indicate a malfunction of the UPS hardware.
- ACTION
If this error appears only rarely, then no action is needed. If it appears
frequently, then call your Hewlett-Packard service representative.
- 568
- MESSAGE
UPS Monitor logic error: Table lookup of what should have
been a valid UPS power status character failed to find the character in the
lookup table. (UPSERR 0568)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 569
- MESSAGE
UPS Monitor logic error: Table lookup of what should have
been a valid UPS alarm status character failed to find the character in the
lookup table. (UPSERR 0569)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 570
- MESSAGE
UPS Monitor logic error: Table lookup of a UPS status
character produced inconsistent results: The lookup procedure declared that
it had found the character, but reported its type as "unknown". (UPSERR 570)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 571
- MESSAGE
UPS Monitor logic error: After deciding that a UPS status
character was valid, the UPS Monitor then failed to find that status
character in its status lookup table. (UPSERR 0571)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 572
- MESSAGE
UPS LDEV ! I/O operation error: The I/O completion status
reported for the UPS I/O operation had an incorrect, unexpected I/O subsystem
number in it. (UPSERR 0572)
- CAUSE
This is a software-detected error condition that indicates an error in the I/O
software subsystems that the UPS Monitor uses to communicate with UPS devices.
- ACTION
Call your Hewlett-Packard service representative.
- 573
- MESSAGE
UPS LDEV ! initialization error: After trying several
times, the UPS Monitor has been unable to complete the initialization
sequence of I/O operations for this UPS device. (UPSERR 0573)
- CAUSE
Something is preventing the HP3000 system from communicating with the UPS.
Possibly a bad I/O interface cable or bad I/O interface hardware at the system
or at the UPS. Possibly a UPS hardware malfunction.
- ACTION
Check the I/O interface cable for correct attachment, and check that the UPS is
powered-on. Check that the system I/O configuration is correct. If the prob-
lem is not found, then call your Hewlett-Packard service representative.
- 574
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Simple_Create_Process. (UPSERR 0574)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 575
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Find_Plabel_Info. (UPSERR 0575)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative
- 576
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure HPgetsysplabel. (UPSERR 0576)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 577
- MESSAGE
UPS Monitor warning: Too many UPS devices have been configured in
the system I/O configuration files. The UPS Monitor can not monitor all of
them; it will monitor as many as it can. (UPSWRN 0577)
- CAUSE
Incorrect system I/O configuration. The system I/O configuration, generated
by SYSGEN and NMMGR configurators, contains more than 128 UPS devices, which is
the maximum number that the UPS monitor can handle simultaneously.
- ACTION
Review and correct the system I/O configuration, reducing the number of UPS
devices specified in the configuration to an acceptable number.
- 578
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Start_Shut_NM. (UPSERR 0578)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 579
- MESSAGE
UPS Monitor logic error: UPS Monitor attempted to create a
"zero size" UPS Table. (UPSERR 0579)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 580
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure HPFOPEN. (UPSERR 0580)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 581
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure FCLOSE. (UPSERR 0581)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 582
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Release_Object. (UPSERR 0582)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 583
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Create_Object. (UPSERR 0583)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 584
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Create_Port. (UPSERR 0584)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 585
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Purge_Port. (UPSERR 0585)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 586
- MESSAGE
UPS Monitor error: UPS Monitor was unable to create its UPS
Table object. The UPS Monitor process can not operate without it, and isaborting itself. (UPSERR 0586)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 587
- MESSAGE
UPS Monitor UPS error: Unable to start monitoring on UPS Ldev !
due to File System error in finding or opening the device. (UPSWRN 0587)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 588
- MESSAGE
UPS Monitor logic error: UPS Monitor has detected that it
has declared a UPS device to be "down", but the status that tells the reason
for the "down" is invalid/undefined. (UPSERR 0588)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 589
- MESSAGE
UPS LDEV ! initialization error: UPS Monitor was unable to
allocate (open) this UPS device. This UPS device will not be monitored.
(UPSERR 0589)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 590
- MESSAGE
UPS Monitor error: UPS Monitor process initialization
failed due to error in obtaining resources (data object, message port, etc.).
(UPSERR 0590)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 591
- MESSAGE
UPS Monitor warning: UPS Monitor finds no UPS devices
configured in the system I/O configuration files. UPS Monitor is terminating
itself. (UPSWRN 0591)
- CAUSE
No UPSs have been configured in the system's I/O configuration files. This is
an error if this system is supposed to have UPSs on it. This is not an error
if this system is not supposed to have UPS devices on it.
- ACTION
If this system is supposed to have UPS devices on it, then review and correct
the system I/O configuration, and then restart the system. If this system is
not supposed to have UPS devices on it, then no action is needed.
- 592
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Ups_Devices_Count. (UPSERR 0592)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 593
- MESSAGE
UPS LDEV ! initialization error: UPS Monitor was unable to
locate this UPS LDEV via the File System's "Device Files" facility. (UPSERR
0593)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 594
- MESSAGE
UPS Monitor logic error: Attempted to do status character
mapping (table lookup) of an unknown/undefined UPS status character. (UPSERR
0594
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 595
- MESSAGE
UPS Monitor information: UPS Monitor process has been
launched by PROGEN and is starting-up its operation. (UPSWRN 0595)
- CAUSE
The system has just been started-up, and the UPS Monitor software subsystem
has automatically been started as well.
- ACTION
No action is needed. This is merely an informational message confirming that
the UPS Monitor software has been started.
- 596
- MESSAGE
UPS Monitor information: UPS Monitor process has initialized
itself successfully, and is ready to start UPS monitoring operations. (UPSWRN
0596)
- CAUSE
After the UPS Monitor process was first started, it successfully initialized
itself: it acquired the basic resources it needed to commence operations.
- ACTION
No action is needed. This is merely an informational message that confirms
that the UPS Monitor completed its process initialization successfully.
- 597
- MESSAGE
UPS Monitor information: UPS Monitor process is shutting
down, due to a normal system shutdown. (UPSWRN 0597)
- CAUSE
The system operator initiated a normal Control-A Shutdown of the MPE/iX system.
The UPS Monitor is shutting itself down as part of the overall system shutdown.
- ACTION
No action is needed. This is merely an informational message that confirms
that the UPS Monitor is shutting down due to a normal system shutdown.
- 598
- MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Ups_Devices_List. (UPSERR 0598)
- CAUSE
This is a software-detected error condition that indicates an error occurred in
a call to the specified MPE/iX Operating System procedure when that procedure
was called by the UPS Monitor software.
- ACTION
Call your Hewlett-Packard service representative.
- 599
- MESSAGE
UPS Monitor warning: UPS Monitor process is shutting down
and restarting itself due to an internal error condition. (UPSWRN 0599)
- CAUSE
The UPS Monitor detected an error condition internal to its software, and is
attempting to recover by restarting itself from the beginning of its process.
- ACTION
If this warning appears only rarely, then no action is needed. If it appears
frequently, then call your Hewlett-Packard service representative.
- 600
- MESSAGE
UPS Monitor error: UPS Monitor process is shutting down,
due to an unrecoverable internal error condition. (UPSERR 0600)
- CAUSE
The UPS Monitor software detected an error condition within its processing from
which it can not recover. Accordingly, it is shutting itself down, ending the
UPS monitoring processing.
- ACTION
This should rarely, if ever, happen in practice. You can re-boot the system to
see if the UPS Monitor will run successfully after a new startup of the system.
If the problem persists, call your Hewlett-Packard service representative.
- 601
- MESSAGE
UPS Monitor logic error: UPS Monitor process unable to
obtain list of UPS LDEVS from HLIO after successfully obtaining number of UPS
devices from HLIO. (UPSERR 0601)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
- 602
- MESSAGE
UPS Monitor information: UPS Monitor process startup of UPS
devices failed, due to inability to get UPS devices' allocation information
from the system. (UPSERR 0602)
- CAUSE
This is a software-detected error condition that indicates an error in the UPS
Monitor software or in some other system software, or a system memory error.
- ACTION
Call your Hewlett-Packard service representative.
|