Ap C. UPS Console Messages [ HP 3000 Series 9X8LX Computer Systems Getting Started ] MPE/iX 5.0 Documentation
HP 3000 Series 9X8LX Computer Systems Getting Started
Appendix C UPS Console Messages
Appendix C describes console messages that only occur while you are using
the UPS.
________________________________________________________________________
MESSAGE: UPS LDEV! reports loss of AC input power. (UPSERR
0033)
CAUSE The specified UPS device reported that it detected
an input power failure. There has been an AC power
failure somewhere in the power path leading into
the UPS. The UPS has switched to its internal
battery pack to supply reserve power.
ACTION If the power failure is brief, not long enough to
exhaust the UPS battery, no action is needed.
Otherwise, determine what is causing the power loss
and take action to restore the power before the UPS
battery becomes exhausted.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports AC input power "Bypass Mode".
(UPSWRN 0035)
CAUSE The specified UPS device has been placed into its
"AC Power Bypass Mode" of operation. This should
only occur when an HP Customer Engineer is
servicing the UPS and intends to put the UPS into
"Bypass Mode".
ACTION: No action is needed if this message occurs during
Customer Engineer servicing of the UPS. If this
message occurs during normal system operation,
there is probably a hardware problem in the UPS.
Call your HP service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports AC input power restored. (UPSWRN
0036)
CAUSE: The specified UPS device had lost its AC input
power in the past, and now the AC input power has
been restored. If the UPS is operating correctly,
it will now switch from battery operation back to
normal AC power operation.
ACTION: No action is needed. The system automatically
returns to normal operation when all UPS devices
(there may be one or several UPS devices on a
system) detect that normal AC input power is
present following a power loss at any UPS.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports "Low Battery Charge" condition.
(UPSWRN 0037)
CAUSE: The specified UPS had lost its AC input power some
time ago and has been supplying reserve power from
its battery. AC input power has not been restored
yet, causing the battery to be drained down to a
"low charge" power level.
ACTION: Locate and correct the cause of the AC power
failure. If AC power is not restored within the
next two minutes, the UPS battery will be exhausted
and the UPS output AC power will fail, causing
power loss to the computer equipment.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports AC output power turned off.
(UPSERR 0041)
CAUSE: The specified UPS device has turned off its AC
output power. Someone may have mistakenly turned
off the UPS' power switch, or the UPS may have
malfunctioned. Whatever equipment was receiving
power from the UPS has now lost power.
ACTION: Investigate and correct the problem at the UPS.
Turn on all power control switches on the UPS. If
the computer (CPU) lost power, you will have to
re-boot the system after restoring the UPS power.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "System Fail" condition
cleared. (UPSWRN 0128)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "System Failure" condition. Now,
the "System Failure" condition within the UPS
device has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Inverter Fail" condition
cleared. (UPSWRN 0129)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Inverter Failure" condition. Now,
the "Inverter Failure" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Battery Not Present"
condition cleared. (UPSWRN 0130)
CAUSE: Some time ago, the specified UPS device had
reported a "Battery Not Present" condition. Now,
the "Battery Not Present" condition within the UPS
has been corrected and the UPS is reporting that it
has returned to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Charger Fault" condition
cleared. (UPSWRN 0131)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Charger Fault" condition. Now, the
"Charger Fault" condition within the UPS device has
been corrected and the UPS is reporting that it has
returned to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Overload Shutdown"
condition cleared. (UPSWRN 0132)
CAUSE: Some time ago, the specified UPS device had
reported an "Overload Shutdown" condition. Now,
the "Overload Shutdown" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Ambient Temperature
Shutdown" condition cleared. (UPSWRN 0133)
CAUSE: Some time ago, the specified UPS device had
reported a "UPS High Ambient Temperature Shutdown"
condition. Now, the "High-Ambient Temperature
Shutdown" condition has been corrected. The UPS is
reporting a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Overload" condition
cleared. (UPSWRN 0134)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Overload" condition. Now, the UPS
"Overload" condition has been corrected and the UPS
is reporting that it has returned to normal
operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Ambient Temperature"
condition cleared. (UPSWRN 0135)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "High Ambient Temp- erature"
condition. Now, the "High Ambient Temperature"
condition has been corrected and the UPS is
reporting that it has returned to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Battery Test Fail"
condition cleared. (UPSWRN 0136)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Battery Test Fail" condition. Now,
the "Battery Test Fail" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Battery Voltage"
condition cleared. (UPSWRN 0137)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "High Battery Volt- age" condition.
Now, the "High Battery Voltage" condition in the
UPS device has been corrected and the UPS is
reporting a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Low Battery Voltage"
condition cleared. (UPSWRN 0138)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Low Battery Volt- age" condition.
Now, the "Low Battery Voltage" condition in the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Output Voltage
Shutdown" condition cleared. (UPSWRN 0139)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "High Output Volt- age Shutdown"
condition. Now, the "High Output Voltage Shutdown"
condition has been cleared and the UPS is reporting
a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Low Output Voltage
Shutdown" condition cleared. (UPSWRN 0140)
CAUSE: Some time ago, the specified UPS device had
reported a UPS "Low Output Voltage Shutdown"
condition. Now, the "Low Output Voltage Shutdown"
condition has been corrected and the UPS is
reporting a return to normal operation.
ACTION: No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "System Fail" condition.
(UPSERR 0192)
CAUSE: The specified UPS device reported a UPS "System
Failure" condition. This is a hardware malfunction
condition within the UPS.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Inverter Fail" condition.
(UPSERR 0193)
CAUSE: The specified UPS device reported a "UPS Inverter
Fail" condition. This is a hardware malfunction
condition within the UPS. The DC-to-AC power
inverter within the UPS has malfunctioned.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Battery Not Present"
condition. (UPSERR 0194)
CAUSE: The specified UPS device reported a "Battery Not
Present" condition. This is a hardware malfunction
condition within the UPS. The UPS hardware logic
perceives that the UPS battery pack is not
connected.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Charger Fault" condition.
(UPSERR 0195)
CAUSE: The specified UPS device reported a UPS "Charger
Fault" condition. This is a hardware malfunction
condition within the UPS. The UPS' internal battery
charger circuitry has malfunctioned.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Overload Shutdown"
condition. (UPSERR 0196)
CAUSE: The specified UPS device reported a UPS "Overload
Shutdown" condition. Too much power was being
drawn from the UPS AC output by the computer
equipment being powered from this UPS. That
equipment may be malfunctioning.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Ambient Temperature
Shutdown" condition. (UPSERR 0197)
CAUSE: The specified UPS device reported a UPS "High
Ambient Temperature Shutdown" condition. The
temperature of the UPS hardware became too high to
permit safe operation, and the UPS turned itself
off to prevent equipment damage.
ACTION: If the computer room has become too warm, take
steps to cool the room. If room temperature is not
the problem, there has probably been a hardware
malfunction. Call your Hewlett-Packard service
representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Overload" condition.
(UPSERR 0198)
CAUSE: The specified UPS device reported a UPS "Overload"
condition. The equipment being powered by the UPS
is drawing too much power from the UPS AC output.
If the excessive power draw continues, the UPS may
reach an "Overload Shutdown".
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Ambient Temperature"
condition. (UPSERR 0199)
CAUSE: The specified UPS device reported a UPS "High
Ambient Temperature" condition. The UPS has
detected an abnormally high temperature in the UPS
hardware. If the temperature rises further, the
UPS may reach "High Temperature Shutdown".
ACTION: If the computer room has become too warm, take
steps to cool the room. If room temperature is not
the problem, there has probably been a hardware
malfunction. Call your Hewlett-Packard service
representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Battery Test Fail"
condition. (UPSERR 0200)
CAUSE: The specified UPS device reported a UPS "Battery
Test Fail" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Battery Voltage"
condition. (UPSERR 0201)
CAUSE: The specified UPS device reported a UPS "High
Battery Voltage" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Low Battery Voltage"
condition. (UPSERR 0202)
CAUSE: The specified UPS device reported a UPS "Low
Battery Voltage" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "High Output Voltage
Shutdown" condition. (UPSERR 0203)
CAUSE: The specified UPS device reported a UPS "High
Output Voltage Shutdown" condi- tion. This is a
hardware malfunction within the UPS hardware or
possibly in the equipment being powered from the
UPS. The UPS has shut itself off.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! reports UPS "Low Output Voltage
Shutdown" condition. (UPSERR 0204)
CAUSE: The specified UPS device reported a UPS "Low Output
Voltage Shutdown" condition. This is a hardware
malfunction within the UPS hardware or possibly in
the equipment being powered from the UPS. The UPS
has shut itself off.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor UPS error: Lost communications with UPS
LDEV !. That UPS is no longer being monitored.
(UPSERR 0512)
CAUSE: The UPS Monitor had been monitoring the specified
UPS LDEV successfully, then for some reason lost
I/O communications with that UPS. The I/O interface
cable or I/O interface hardware may have failed, or
the UPS itself may have failed.
ACTION: Check the specified UPS's I/O interface cable and
I/O interface connection at the computer. Check
the UPS hardware for power connections and front
panel indicators. If the cause is not found, call
your HP service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation warning: Warning status
returned by I/O system at completion of a UPS I/O
request. (UPSWRN 0533)
CAUSE: This is a software-detected warning condition that
indicates something unusual occurred in an I/O
request made to a UPS by the UPS Monitor.
ACTION: If this warning appears only rarely, then no action
is needed. If it appears frequently, then call
your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation error: Error status
returned by I/O system at completion of a UPS I/O
request. (UPSERR 0534)
CAUSE: This is a software-detected error condition that
indicates an error in the I/O software subsystems
that the UPS Monitor uses to communicate with UPS
devices.
ACTION: If this error appears only rarely, then no action
is needed. If it appears frequently, then call
your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation error: A status of
"aborted" was returned by I/O system as completion
status of a UPS I/O request. (UPSERR 0535)
CAUSE: This is a software-detected error condition that
indicates an error in the I/O software subsystems
that the UPS Monitor uses to communicate with UPS
devices.
ACTION: If this error appears only rarely, then no action
is needed. If it appears frequently, then call
your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation error: UPS device failed
to complete a Read I/O request in allotted time.
The Read request timed out. (UPSERR 0536)
CAUSE: This is a software-detected error condition that
indicates an error in the I/O software subsystems
that the UPS Monitor uses to communicate with UPS
devices. It could indicate a disconnected I/O
cable or a UPS hardware malfunction.
ACTION: Check for proper connection of the UPS I/O
interface cable at both ends. See if the UPS is
powered-on. If those checks do not reveal
the source of the problem, then call your
Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS Monitor UPS initialization: UPS LDEV ! was
initialized successfully and is now being
monitored. (UPSWRN 0540)
CAUSE: During system startup, the specified UPS device was
successfully initialized by the UPS Monitor.
ACTION: No action is needed. This is merely an expected
confirmation that the UPS and UPS Monitor software
are operating correctly.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation error: The actual Read
data transfer length in a UPS Read I/O operation
was too short, less than the minimum required Read
transfer length. (UPSERR 0563)
CAUSE: This is a software-detected error condition that
indicates an error in the I/O software subsystems
that the UPS Monitor uses to communicate with UPS
devices. It could also indicate an I/O interface
hardware error, or a UPS hardware error
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O Operation error: The actual Read
data transfer length in a UPS Read I/O operation
was too long, greater than the maximum requested
Read transfer length. (UPSERR 0564)
CAUSE: This is a software-detected error condition that
indicates an error in the I/O software subsystems
that the UPS Monitor uses to communicate with UPS
devices. It could also indicate an I/O interface
error or a UPS hardware error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS LDEV ! I/O operation error: Data supplied by
the UPS device in response to a Read I/O request
did not match any of the allowable data patterns
for that request. The Read will be re-done. (UPSERR
0567)
CAUSE: Possibly a poor I/O interface cable connection
between the system and the UPS. Possibly electrical
noise interference induced in the I/O interface
cable or hardware. It could also indicate a
malfunction of the UPS hardware.
ACTION: If this error appears only rarely, then no action
is needed. If it appears frequently, then call
your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! initialization error: After trying
several times, the UPS Monitor has been unable to
complete the initialization sequence of I/O
operations for this UPS device. (UPSERR 0573)
CAUSE: Something is preventing the HP3000 system from
communicating with the UPS. Possibly a bad I/O
interface cable or bad I/O interface hardware at
the system or at the UPS. Possibly a UPS hardware
malfunction.
ACTION: Check the I/O interface cable for correct
attachment, and check that the UPS is powered-on.
Check that the system I/O configuration is correct.
If the problem is not found, then call your
Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor warning: Too many UPS devices have been
configured in the system I/O configuration files.
The UPS Monitor can not monitor all of them; it
will monitor as many as it can. (UPSWRN 0577)
CAUSE: Incorrect system I/O configuration. The system I/O
configuration, generated by SYSGEN and NMMGR
configurators, contains more than 128 UPS devices,
which is the maximum number that the UPS monitor
can handle simultaneously.
ACTION: Review and correct the system I/O configuration,
reducing the number of UPS devices specified in the
configuration to an acceptable number.
________________________________________________________________________
MESSAGE: UPS Monitor system call error: Error status !
(Subsystem # !, Error # !) received from procedure
HPFOPEN. (UPSERR 0580)
CAUSE: This is a software-detected error condition that
indicates an error occurred in a call to the
specified MPE/iX operating system procedure when
that procedure was called by the UPS Monitor
software.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor system call error: Error status !
(Subsystem # !, Error # !) received from procedure
FCLOSE. (UPSERR 0581)
CAUSE: This is a software-detected error condition that
indicates an error occurred in a call to the
specified MPE/iX Operating System procedure when
that procedure was called by the UPS Monitor
software.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS Monitor system call error: Error status !
(Subsystem # !, Error # !) received from procedure
Create_Port. (UPSERR 0584)
CAUSE: This is a software-detected error condition that
indicates an error occurred in a call to the
specified MPE/iX Operating System procedure when
that procedure was called by the UPS Monitor
software.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor system call error: Error status !
(Subsystem # !, Error # !) received from procedure
Purge_Port. (UPSERR 0585)
CAUSE: This is a software-detected error condition that
indicates an error occurred in a call to the
specified MPE/iX Operating System procedure when
that procedure was called by the UPS Monitor
software.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS Monitor error: UPS Monitor was unable to create
its UPS Table object. The UPS Monitor process can
not operate without it, and is aborting itself.
(UPSERR 0586)
CAUSE: This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor UPS error: Unable to start monitoring
on UPS Ldev ! due to File System error in finding
or opening the device. (UPSWRN 0587)
CAUSE: This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS LDEV ! initialization error: UPS Monitor was
unable to allocate (open) this UPS device. This UPS
device will not be monitored. (UPSERR 0589)
CAUSE: This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor error: UPS Monitor process
initialization failed due to error in obtaining
resources (data object, message port, etc.).
(UPSERR 0590)
CAUSE: This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS Monitor warning: UPS Monitor finds no UPS
devices configured in the system I/O configuration
files. UPS Monitor is terminating itself. (UPSWRN
0591)
CAUSE: No UPSs have been configured in the system's I/O
configuration files. This is an error if this
system is supposed to have UPSs on it. This is not
an error if this system is not supposed to have UPS
devices on it.
ACTION: If this system is supposed to have UPS devices on
it, then review and correct the system I/O
configuration, and then restart the system. If
this system is not supposed to have UPS devices on
it, then no action is needed.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor information: UPS Monitor process has
been launched by PROGEN and is starting-up its
operation. (UPSWRN 0595)
CAUSE: The system has just been started-up, and the UPS
Monitor software subsystem has automatically been
started as well.
ACTION: No action is needed. This is merely an
informational message confirming that the UPS
Monitor software has been started.
________________________________________________________________________
MESSAGE: UPS Monitor information: UPS Monitor process has
initialized itself successfully, and is ready to
start UPS monitoring operations. (UPSWRN 0596)
CAUSE: After the UPS Monitor process was first started, it
successfully initialized itself: it acquired the
basic resources it needed to commence operations.
ACTION: No action is needed. This is merely an
informational message that confirms that the UPS
Monitor completed its process initialization
successfully.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor information: UPS Monitor process is
shutting down, due to a normal system shutdown.
(UPSWRN 0597)
CAUSE: The system operator initiated a normal Control-A
Shutdown of the MPE/iX system. The UPS Monitor is
shutting itself down as part of the overall system
shutdown.
ACTION: No action is needed. This is merely an
informational message that confirms that the UPS
Monitor is shutting down due to a normal system
shutdown.
________________________________________________________________________
MESSAGE: UPS Monitor warning: UPS Monitor process is
shutting down and restarting itself due to an
internal error condition. (UPSWRN 0599)
CAUSE: The UPS Monitor detected an error condition
internal to its software, and is attempting to
recover by restarting itself from the beginning of
its process.
ACTION: If this warning appears only rarely, then no action
is needed. If it appears frequently, then call
your Hewlett-Packard representative.
________________________________________________________________________
________________________________________________________________________
MESSAGE: UPS Monitor error: UPS Monitor process is shutting
down, due to an unrecoverable internal error
condition. (UPSERR 0600)
CAUSE: The UPS Monitor software detected an error
condition within its processing from which it can
not recover. Accordingly, it is shutting itself
down, ending the UPS monitoring processing.
ACTION: This should rarely, if ever, happen in practice.
You can re-boot the system to see if the UPS
Monitor will run successfully after a new startup
of the system. If the problem persists, call your
Hewlett-Packard service representative.
________________________________________________________________________
MESSAGE: UPS Monitor information: UPS Monitor process
startup of UPS devices failed, due to inability to
get UPS devices' allocation information from the
system. (UPSERR 0602)
CAUSE: This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION: Call your Hewlett-Packard service representative.
________________________________________________________________________