33 MESSAGE UPS LDEV ! reports loss of AC input power.
(UPSERR 0033)
CAUSE The specified UPS device reported that it detected
an input power failure. There has been an AC power
failure somewhere in the power path leading into
the UPS. The UPS has switched to its internal
battery pack to supply reserve power.
ACTION If the power failure is brief, not long enough to
exhaust the UPS battery, no action is needed.
Otherwise, determine what is causing the power loss
and take action to restore the power before the UPS
battery becomes exhausted.
-------------------------------------------------------------
35 MESSAGE UPS LDEV ! reports AC input power "Bypass Mode".
(UPSWRN 0035)
CAUSE The specified UPS device has been placed into its
"AC Power Bypass Mode" of operation. This should
only occur when an HP Customer Engineer is
servicing the UPS and intends to put the UPS into
"Bypass Mode".
ACTION No action is needed if this message occurs during
Customer Engineer servicing of the UPS. If this
message occurs during normal system operation,
there is probably a hardware problem in the UPS.
Call your HP service representative.
-------------------------------------------------------------
36 MESSAGE UPS LDEV ! reports AC input power restored.
(UPSWRN 0036)
CAUSE The specified UPS device had lost its AC input
power in the past, and now the AC input power has
been restored. If the UPS is operating correctly,
it will now switch from battery operation back to
normal AC power operation.
ACTION No action is needed. The system automatically
returns to normal operation when all UPS devices
(there may be one or several UPS devices on a
system) detect that normal AC input power is
present following a power loss at any UPS.
-------------------------------------------------------------
37 MESSAGE UPS LDEV ! reports "Low Battery Charge"
condition. (UPSWRN 0037)
CAUSE The specified UPS had lost its AC input power some
time ago and has been supplying reserve power from
its battery. AC input power has not been restored
yet, causing the battery to be drained down to a
"low charge" power level.
ACTION Locate and correct the cause of the AC power
failure. If AC power is not restored within the
next two minutes, the UPS battery will be exhausted
and the UPS output AC power will fail, causing
power loss to the computer equipment.
-------------------------------------------------------------
41 MESSAGE UPS LDEV ! reports AC output power turned off.
(UPSERR 0041)
CAUSE The specified UPS device has turned off its AC
output power. Someone may have mistakenly turned
off the UPS' power switch, or the UPS may have
malfunctioned. Whatever equipment was receiving
power from the UPS has now lost power.
ACTION Investigate and correct the problem at the UPS.
Turn on all power control switches on the UPS. If
the computer (CPU) lost power, you will have to
re-boot the system after restoring the UPS power.
-------------------------------------------------------------
128 MESSAGE UPS LDEV ! reports UPS "System Fail" condition
cleared. (UPSWRN 0128)
CAUSE Some time ago, the specified UPS device had
reported a UPS "System Failure" condition. Now,
the "System Failure" condition within the UPS
device has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
129 MESSAGE UPS LDEV ! reports UPS "Inverter Fail" condition
cleared. (UPSWRN 0129)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Inverter Failure" condition. Now,
the "Inverter Failure" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
130 MESSAGE UPS LDEV ! reports UPS "Battery Not Present"
condition cleared. (UPSWRN 0130)
CAUSE Some time ago, the specified UPS device had
reported a "Battery Not Present" condition. Now,
the "Battery Not Present" condition within the UPS
has been corrected and the UPS is reporting that it
has returned to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
131 MESSAGE UPS LDEV ! reports UPS "Charger Fault" condition
cleared. (UPSWRN 0131)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Charger Fault" condition. Now, the
"Charger Fault" condition within the UPS device has
been corrected and the UPS is reporting that it has
returned to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
132 MESSAGE UPS LDEV ! reports UPS "Overload Shutdown"
condition cleared. (UPSWRN 0132)
CAUSE Some time ago, the specified UPS device had
reported an "Overload Shutdown" condition. Now,
the "Overload Shutdown" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
133 MESSAGE UPS LDEV ! reports UPS "High Ambient Temperature
Shutdown" condition cleared. (UPSWRN 0133)
CAUSE Some time ago, the specified UPS device had
reported a "UPS High Ambient Temp- erature
Shutdown" condition. Now, the "High-Ambient
Temperature Shutdown" con- dition has been
corrected. The UPS is reporting a return to normal
operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
134 MESSAGE UPS LDEV ! reports UPS "Overload" condition
cleared. (UPSWRN 134)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Overload" condition. Now, the UPS
"Overload" condition has been corrected and the UPS
is reporting that it has returned to normal
operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
135 MESSAGE UPS LDEV ! reports UPS "High Ambient Temperature"
condition cleared. (UPSWRN 0135)
CAUSE Some time ago, the specified UPS device had
reported a UPS "High Ambient Temp- erature"
condition. Now, the "High Ambient Temperature"
condition has been corrected and the UPS is
reporting that it has returned to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
136 MESSAGE UPS LDEV ! reports UPS "Battery Test Fail"
condition cleared. (UPSWRN 0136)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Battery Test Fail" condition. Now,
the "Battery Test Fail" condition within the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
137 MESSAGE UPS LDEV ! reports UPS "High Battery Voltage"
condition cleared. (UPSWRN 0137)
CAUSE Some time ago, the specified UPS device had
reported a UPS "High Battery Volt- age" condition.
Now, the "High Battery Voltage" condition in the
UPS device has been corrected and the UPS is
reporting a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
138 MESSAGE UPS LDEV ! reports UPS "Low Battery Voltage"
condition cleared. (UPSWRN 0138)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Low Battery Volt- age" condition.
Now, the "Low Battery Voltage" condition in the UPS
device has been corrected and the UPS is reporting
a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
139 MESSAGE UPS LDEV ! reports UPS "High Output Voltage
Shutdown" condition cleared. (UPSWRN 0139)
CAUSE Some time ago, the specified UPS device had
reported a UPS "High Output Volt- age Shutdown"
condition. Now, the "High Output Voltage Shutdown"
condition has been cleared and the UPS is reporting
a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
140 MESSAGE UPS LDEV ! reports UPS "Low Output Voltage
Shutdown" condition cleared. (UPSWRN 0140)
CAUSE Some time ago, the specified UPS device had
reported a UPS "Low Output Voltage Shutdown"
condition. Now, the "Low Output Voltage Shutdown"
condition has been corrected and the UPS is
reporting a return to normal operation.
ACTION No action is needed. This message merely confirms
that a previously reported problem has been
corrected.
-------------------------------------------------------------
192 MESSAGE UPS LDEV ! reports UPS "System Fail" condition.
(UPSERR 0192)
CAUSE The specified UPS device reported a UPS "System
Failure" condition. This is a hardware malfunction
condition within the UPS.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
193 MESSAGE UPS LDEV ! reports UPS "Inverter Fail" condition.
(UPSERR 0193)
CAUSE The specified UPS device reported a "UPS Inverter
Fail" condition. This is a hardware malfunction
condition within the UPS. The DC-to-AC power
inverter within the UPS has malfunctioned.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
194 MESSAGE UPS LDEV ! reports UPS "Battery Not Present"
condition. (UPSERR 0194)
CAUSE The specified UPS device reported a "Battery Not
Present" condition. This is a hardware malfunction
condition within the UPS. The UPS hardware logic
perceives that the UPS battery pack is not
connected.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
195 MESSAGE UPS LDEV ! reports UPS "Charger Fault" condition.
(UPSERR 0195)
CAUSE The specified UPS device reported a UPS "Charger
Fault" condition. This is a hardware malfunction
condition within the UPS. The UPS' internal battery
charger circuitry has malfunctioned.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
196 MESSAGE UPS LDEV ! reports UPS "Overload Shutdown"
condition. (UPSERR 0196)
\CAUSE\ The specified UPS device reported a UPS
"Overload Shutdown" condition. Too much power was
being drawn from the UPS AC output by the computer
equipment being powered from this UPS. That
equipment may be malfunctioning.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
197 MESSAGE UPS LDEV ! reports UPS "High Ambient Temperature
Shutdown" condition. (UPSERR 0197)
CAUSE The specified UPS device reported a UPS "High
Ambient Temperature Shutdown" condition. The
temperature of the UPS hardware became too high to
permit safe operation, and the UPS turned itself
off to prevent equipment damage.
ACTION If the computer room has become too warm, take
steps to cool the room. If room temperature is not
the problem, there has probably been a hardware
malfunction. Call your Hewlett-Packard service
representative.
-------------------------------------------------------------
198 MESSAGE UPS LDEV ! reports UPS "Overload" condition.
(UPSERR 0198)
CAUSE The specified UPS device reported a UPS "Overload"
condition. The equipment being powered by the UPS
is drawing too much power from the UPS AC output.
If the excessive power draw continues, the UPS may
reach an "Overload Shutdown".
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
199 MESSAGE UPS LDEV ! reports UPS "High Ambient Temperature"
condition. (UPSERR 0199)
CAUSE The specified UPS device reported a UPS "High
Ambient Temperature" condition. The UPS has
detected an abnormally high temperature in the UPS
hardware. If the temperature rises further, the
UPS may reach "High Temperature Shutdown".
ACTION If the computer room has become too warm, take
steps to cool the room. If room temperature is not
the problem, there has probably been a hardware
malfunction. Call your Hewlett-Packard service
representative.
-------------------------------------------------------------
200 MESSAGE UPS LDEV ! reports UPS "Battery Test Fail"
condition. (UPSERR 0200)
CAUSE The specified UPS device reported a UPS "Battery
Test Fail" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
201 MESSAGE UPS LDEV ! reports UPS "High Battery Voltage"
condition. (UPSERR 0201)
CAUSE The specified UPS device reported a UPS "High
Battery Voltage" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
202 MESSAGE UPS LDEV ! reports UPS "Low Battery Voltage"
condition. (UPSERR 0202)
CAUSE The specified UPS device reported a UPS "Low
Battery Voltage" condition. This is a hardware
malfunction within the UPS hardware. The UPS logic
perceives that the UPS battery is not working
properly.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
203 MESSAGE UPS LDEV ! reports UPS "High Output Voltage
Shutdown" condition. (UPSERR 0203)
CAUSE The specified UPS device reported a UPS "High
Output Voltage Shutdown" condi- tion. This is a
hardware malfunction within the UPS hardware or
possibly in the equipment being powered from the
UPS. The UPS has shut itself off.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
204 MESSAGE UPS LDEV ! reports UPS "Low Output Voltage
Shutdown" condition. (UPSERR 0204)
CAUSE The specified UPS device reported a UPS "Low Output
Voltage Shutdown" condition. This is a hardware
malfunction within the UPS hardware or possibly in
the equipment being powered from the UPS. The UPS
has shut itself off.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
512 MESSAGE UPS Monitor UPS error: Lost communications with
UPS LDEV !. That UPS is no longer being monitored.
(UPSERR 0512)
CAUSE The UPS Monitor had been monitoring the specified
UPS LDEV successfully, then for some reason lost
I/O communications with that UPS. The I/O interface
cable or I/O interface hardware may have failed, or
the UPS itself may have failed.
ACTION Check the specified UPS's I/O interface cable and
I/O interface connection at the computer. Check
the UPS hardware for power connections and front
panel indicators. If the cause is not found, call
your HP service representative.
-------------------------------------------------------------
513 MESSAGE UPS Monitor logic error: Attempted to map an
invalid UPS power status condition. (UPSERR 0513)
CAUSE This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------
514 MESSAGE UPS Monitor logic error: Attempted to map an
invalid UPS alarm status condition. (UPSERR 0514)
CAUSE This is a software-detected error condition that
indicates an error in the UPS Monitor software or
in some other system software, or a system memory
error.
ACTION Call your Hewlett-Packard service representative.
-------------------------------------------------------------