Chapter 35  UPS 

(Uninterrupted Power Source) 

------------------------------------------------------------

-------------------------------------------------------------

33           MESSAGE    UPS LDEV ! reports loss of AC input power.
                      (UPSERR 0033)

           CAUSE      The specified UPS device reported that it detected
                      an input power failure.  There has been an AC power
                      failure somewhere in the power path leading into
                      the UPS. The UPS has switched to its internal
                      battery pack to supply reserve power.

           ACTION     If the power failure is brief, not long enough to
                      exhaust the UPS battery, no action is needed.
                      Otherwise, determine what is causing the power loss
                      and take action to restore the power before the UPS
                      battery becomes exhausted.

-------------------------------------------------------------

35           MESSAGE    UPS LDEV ! reports AC input power "Bypass Mode".
                      (UPSWRN 0035)

           CAUSE      The specified UPS device has been placed into its
                      "AC Power Bypass Mode" of operation.  This should
                      only occur when an HP Customer Engineer is
                      servicing the UPS and intends to put the UPS into
                      "Bypass Mode".

           ACTION     No action is needed if this message occurs during
                      Customer Engineer servicing of the UPS. If this
                      message occurs during normal system operation,
                      there is probably a hardware problem in the UPS.
                      Call your HP service representative.

-------------------------------------------------------------

36           MESSAGE    UPS LDEV ! reports AC input power restored.
                      (UPSWRN 0036)

           CAUSE      The specified UPS device had lost its AC input
                      power in the past, and now the AC input power has
                      been restored.  If the UPS is operating correctly,
                      it will now switch from battery operation back to
                      normal AC power operation.

           ACTION     No action is needed.  The system automatically
                      returns to normal operation when all UPS devices
                      (there may be one or several UPS devices on a
                      system) detect that normal AC input power is
                      present following a power loss at any UPS.

-------------------------------------------------------------

37           MESSAGE    UPS LDEV ! reports "Low Battery Charge"
                      condition. (UPSWRN 0037)

           CAUSE      The specified UPS had lost its AC input power some
                      time ago and has been supplying reserve power from
                      its battery.  AC input power has not been restored
                      yet, causing the battery to be drained down to a
                      "low charge" power level.

           ACTION     Locate and correct the cause of the AC power
                      failure.  If AC power is not restored within the
                      next two minutes, the UPS battery will be exhausted
                      and the UPS output AC power will fail, causing
                      power loss to the computer equipment.

-------------------------------------------------------------

41           MESSAGE    UPS LDEV ! reports AC output power turned off.
                      (UPSERR 0041)

           CAUSE      The specified UPS device has turned off its AC
                      output power.  Someone may have mistakenly turned
                      off the UPS' power switch, or the UPS may have
                      malfunctioned.  Whatever equipment was receiving
                      power from the UPS has now lost power.

           ACTION     Investigate and correct the problem at the UPS.
                      Turn on all power control switches on the UPS. If
                      the computer (CPU) lost power, you will have to
                      re-boot the system after restoring the UPS power.

-------------------------------------------------------------

128          MESSAGE    UPS LDEV ! reports UPS "System Fail" condition
                      cleared. (UPSWRN 0128)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "System Failure" condition.  Now,
                      the "System Failure" condition within the UPS
                      device has been corrected and the UPS is reporting
                      that it has returned to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

129          MESSAGE    UPS LDEV ! reports UPS "Inverter Fail" condition
                      cleared.  (UPSWRN 0129)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Inverter Failure" condition.  Now,
                      the "Inverter Failure" condition within the UPS
                      device has been corrected and the UPS is reporting
                      a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

130          MESSAGE    UPS LDEV ! reports UPS "Battery Not Present"
                      condition cleared.  (UPSWRN 0130)

           CAUSE      Some time ago, the specified UPS device had
                      reported a "Battery Not Present" condition.  Now,
                      the "Battery Not Present" condition within the UPS
                      has been corrected and the UPS is reporting that it
                      has returned to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

131          MESSAGE    UPS LDEV ! reports UPS "Charger Fault" condition
                      cleared.  (UPSWRN 0131)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Charger Fault" condition.  Now, the
                      "Charger Fault" condition within the UPS device has
                      been corrected and the UPS is reporting that it has
                      returned to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

132          MESSAGE    UPS LDEV ! reports UPS "Overload Shutdown"
                      condition cleared.  (UPSWRN 0132)

           CAUSE      Some time ago, the specified UPS device had
                      reported an "Overload Shutdown" condition.  Now,
                      the "Overload Shutdown" condition within the UPS
                      device has been corrected and the UPS is reporting
                      a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

133          MESSAGE    UPS LDEV ! reports UPS "High Ambient Temperature
                      Shutdown" condition cleared. (UPSWRN 0133)

           CAUSE      Some time ago, the specified UPS device had
                      reported a "UPS High Ambient Temp- erature
                      Shutdown" condition.  Now, the "High-Ambient
                      Temperature Shutdown" con- dition has been
                      corrected.  The UPS is reporting a return to normal
                      operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

134          MESSAGE    UPS LDEV ! reports UPS "Overload" condition
                      cleared. (UPSWRN 134)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Overload" condition.  Now, the UPS
                      "Overload" condition has been corrected and the UPS
                      is reporting that it has returned to normal
                      operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

135          MESSAGE    UPS LDEV ! reports UPS "High Ambient Temperature"
                      condition cleared. (UPSWRN 0135)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "High Ambient Temp- erature"
                      condition.  Now, the "High Ambient Temperature"
                      condition has been corrected and the UPS is
                      reporting that it has returned to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

136          MESSAGE    UPS LDEV ! reports UPS "Battery Test Fail"
                      condition cleared.  (UPSWRN 0136)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Battery Test Fail" condition.  Now,
                      the "Battery Test Fail" condition within the UPS
                      device has been corrected and the UPS is reporting
                      a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

137          MESSAGE    UPS LDEV ! reports UPS "High Battery Voltage"
                      condition cleared.  (UPSWRN 0137)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "High Battery Volt- age" condition.
                      Now, the "High Battery Voltage" condition in the
                      UPS device has been corrected and the UPS is
                      reporting a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

138          MESSAGE    UPS LDEV ! reports UPS "Low Battery Voltage"
                      condition cleared.  (UPSWRN 0138)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Low Battery Volt- age" condition.
                      Now, the "Low Battery Voltage" condition in the UPS
                      device has been corrected and the UPS is reporting
                      a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

139          MESSAGE    UPS LDEV ! reports UPS "High Output Voltage
                      Shutdown" condition cleared. (UPSWRN 0139)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "High Output Volt- age Shutdown"
                      condition.  Now, the "High Output Voltage Shutdown"
                      condition has been cleared and the UPS is reporting
                      a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

140          MESSAGE    UPS LDEV ! reports UPS "Low Output Voltage
                      Shutdown" condition cleared. (UPSWRN 0140)

           CAUSE      Some time ago, the specified UPS device had
                      reported a UPS "Low Output Voltage Shutdown"
                      condition.  Now, the "Low Output Voltage Shutdown"
                      condition has been corrected and the UPS is
                      reporting a return to normal operation.

           ACTION     No action is needed.  This message merely confirms
                      that a previously reported problem has been
                      corrected.

-------------------------------------------------------------

192          MESSAGE    UPS LDEV ! reports UPS "System Fail" condition.
                      (UPSERR 0192)

           CAUSE      The specified UPS device reported a UPS "System
                      Failure" condition.  This is a hardware malfunction
                      condition within the UPS.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

193          MESSAGE    UPS LDEV ! reports UPS "Inverter Fail" condition.
                      (UPSERR 0193)

           CAUSE      The specified UPS device reported a "UPS Inverter
                      Fail" condition.  This is a hardware malfunction
                      condition within the UPS. The DC-to-AC power
                      inverter within the UPS has malfunctioned.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

194          MESSAGE    UPS LDEV ! reports UPS "Battery Not Present"
                      condition. (UPSERR 0194)

           CAUSE      The specified UPS device reported a "Battery Not
                      Present" condition.  This is a hardware malfunction
                      condition within the UPS. The UPS hardware logic
                      perceives that the UPS battery pack is not
                      connected.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

195          MESSAGE    UPS LDEV ! reports UPS "Charger Fault" condition.
                      (UPSERR 0195)

           CAUSE      The specified UPS device reported a UPS "Charger
                      Fault" condition.  This is a hardware malfunction
                      condition within the UPS. The UPS' internal battery
                      charger circuitry has malfunctioned.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

196          MESSAGE    UPS LDEV ! reports UPS "Overload Shutdown"
                      condition. (UPSERR 0196)
                      \CAUSE\ The specified UPS device reported a UPS
                      "Overload Shutdown" condition.  Too much power was
                      being drawn from the UPS AC output by the computer
                      equipment being powered from this UPS. That
                      equipment may be malfunctioning.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

197          MESSAGE    UPS LDEV ! reports UPS "High Ambient Temperature
                      Shutdown" condition. (UPSERR 0197)

           CAUSE      The specified UPS device reported a UPS "High
                      Ambient Temperature Shutdown" condition.  The
                      temperature of the UPS hardware became too high to
                      permit safe operation, and the UPS turned itself
                      off to prevent equipment damage.

           ACTION     If the computer room has become too warm, take
                      steps to cool the room.  If room temperature is not
                      the problem, there has probably been a hardware
                      malfunction.  Call your Hewlett-Packard service
                      representative.

-------------------------------------------------------------

198          MESSAGE    UPS LDEV ! reports UPS "Overload" condition.
                      (UPSERR 0198)

           CAUSE      The specified UPS device reported a UPS "Overload"
                      condition.  The equipment being powered by the UPS
                      is drawing too much power from the UPS AC output.
                      If the excessive power draw continues, the UPS may
                      reach an "Overload Shutdown".

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

199          MESSAGE    UPS LDEV ! reports UPS "High Ambient Temperature"
                      condition.  (UPSERR 0199)

           CAUSE      The specified UPS device reported a UPS "High
                      Ambient Temperature" condition.  The UPS has
                      detected an abnormally high temperature in the UPS
                      hardware.  If the temperature rises further, the
                      UPS may reach "High Temperature Shutdown".

           ACTION     If the computer room has become too warm, take
                      steps to cool the room.  If room temperature is not
                      the problem, there has probably been a hardware
                      malfunction.  Call your Hewlett-Packard service
                      representative.

-------------------------------------------------------------

200          MESSAGE    UPS LDEV ! reports UPS "Battery Test Fail"
                      condition. (UPSERR 0200)

           CAUSE      The specified UPS device reported a UPS "Battery
                      Test Fail" condition.  This is a hardware
                      malfunction within the UPS hardware.  The UPS logic
                      perceives that the UPS battery is not working
                      properly.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

201          MESSAGE    UPS LDEV ! reports UPS "High Battery Voltage"
                      condition.  (UPSERR 0201)

           CAUSE      The specified UPS device reported a UPS "High
                      Battery Voltage" condition.  This is a hardware
                      malfunction within the UPS hardware.  The UPS logic
                      perceives that the UPS battery is not working
                      properly.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

202          MESSAGE    UPS LDEV ! reports UPS "Low Battery Voltage"
                      condition.  (UPSERR 0202)

           CAUSE      The specified UPS device reported a UPS "Low
                      Battery Voltage" condition.  This is a hardware
                      malfunction within the UPS hardware.  The UPS logic
                      perceives that the UPS battery is not working
                      properly.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

203          MESSAGE    UPS LDEV ! reports UPS "High Output Voltage
                      Shutdown" condition.  (UPSERR 0203)

           CAUSE      The specified UPS device reported a UPS "High
                      Output Voltage Shutdown" condi- tion.  This is a
                      hardware malfunction within the UPS hardware or
                      possibly in the equipment being powered from the
                      UPS. The UPS has shut itself off.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

204          MESSAGE    UPS LDEV ! reports UPS "Low Output Voltage
                      Shutdown" condition.  (UPSERR 0204)

           CAUSE      The specified UPS device reported a UPS "Low Output
                      Voltage Shutdown" condition.  This is a hardware
                      malfunction within the UPS hardware or possibly in
                      the equipment being powered from the UPS. The UPS
                      has shut itself off.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

512          MESSAGE    UPS Monitor UPS error: Lost communications with
                      UPS LDEV !.  That UPS is no longer being monitored.
                      (UPSERR 0512)

           CAUSE      The UPS Monitor had been monitoring the specified
                      UPS LDEV successfully, then for some reason lost
                      I/O communications with that UPS. The I/O interface
                      cable or I/O interface hardware may have failed, or
                      the UPS itself may have failed.

           ACTION     Check the specified UPS's I/O interface cable and
                      I/O interface connection at the computer.  Check
                      the UPS hardware for power connections and front
                      panel indicators.  If the cause is not found, call
                      your HP service representative.

-------------------------------------------------------------

513          MESSAGE    UPS Monitor logic error: Attempted to map an
                      invalid UPS power status condition. (UPSERR 0513)

           CAUSE      This is a software-detected error condition that
                      indicates an error in the UPS Monitor software or
                      in some other system software, or a system memory
                      error.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------

514          MESSAGE    UPS Monitor logic error: Attempted to map an
                      invalid UPS alarm status condition.  (UPSERR 0514)

           CAUSE      This is a software-detected error condition that
                      indicates an error in the UPS Monitor software or
                      in some other system software, or a system memory
                      error.

           ACTION     Call your Hewlett-Packard service representative.

-------------------------------------------------------------